Danfoss 134F0368 (FC-202N132T4E20H2XGCXXXSXXXXAXBXCXXXXDX) 150HP 177A IP20 VLT Aqua Drive FC-202
The 134F0368 is an optimised inverter for AC motor driven water and wastewater applications, with a continuous output of 150HP, or 177A and running off a Three Phase 380-480V supply.
User friendly programming makes installation simple and enables owners to reach the maximum level of performance and lowest cost of ownership. Set up the 134F0368 quickly and easily with the user friendly dialogue based Smart Start, and a quick menu. The quick menu provides direct access to the most important features for water and pump applications, by collecting these in one place, the risk of incorrect configuration is reduced significantly.
Featuring a wide selection of powerful, standard features, which can be expanded with performance improving options, the VLT® AQUA Drive is equally suited to both new and retrofit projects. Features such as dry run detection and flow confirmation help to protect your pumps and deragging can be performed as either preventative or reactive cleaning. Motor alternation and cascade controller helps to save energy and reduce equipment costs. These are only a few of the dedicated pumping features of the 134F0368
The 134F0368 is also known as FC-202N132T4E20H2XGCXXXSXXXXAXBXCXXXXDX.
As an approved Danfoss service partner, AFi are also able to offer repairs of the 134F0368, along with field service, installation and commissioning support and selection advice. Our experienced team also provide upgrade advice and implementation and control panel design and build.
134F0368 Specifications
| AC Drive Input Voltage (VAC) | 380-480V |
| AC Drive Heavy Duty Output (HP) | 150 |
| AC Drive Heavy Duty Output (Amps) | 177 |
| AC Drive Heavy Duty Output (kw) | 110 |
| AC Drive Normal Duty Output (HP) | 200 |
| AC Drive Normal Duty Output (kw) | 132 |
| AC Drive Phase | Three Phase |
| AC Drive Protection | IP20 |
| AC Drive Keypad | Yes |
| AC Drive Filter | Class A2 (C3) |
| AC Drive Communications | Modbus Comms |
| AC Drive Loop | Open Loop |
| AC Drive Logic | Positive, Negative |
| AC Drive Nr Digital Inputs | 6 |
| AC Drive Nr Analog Inputs | 2 |
| AC Drive Nr Digital Outputs | 2 |
| AC Drive Nr Analog Outputs | 1 |
| AC Drive Nr Relay Outputs | 2 |
| AC Drive Pulse Input | 2 |
| AC Drive Brake Chopper | No |
| AC Drive Conformal Coating | Yes |
| AC Drive Safe Torque Off | No |